T6 Main Control Unit

Part No.   MCU-02-115 & MCU-04-115

NOTE:

The MCU-04 has an additional serial port located on the side. This port allows the control to interface with an IBM personal computer. It can also be programmed using a pocket programmer. Users of the SKPC must reorder the MCU-04.

The MCU-04 also has an auxiliary supply rated at 10-14 vdc @ 100 ma.

Power Requirements

115VAC @ .02A, 50/60Hz w/1000v magnetic isolation

Outputs

4 normally open relay contacts unprotected, no leakage current

5Amps @ 230VAC (resistive load), 250 VA (inductive load)

Response time: 10ms operate / 5ms release

Rated life: 5 million (mech) / 200,000 @ 3A (resistive load)

Inputs

6 self powered, 12-14 VDC @ 10ma. w/ 1000v optical isolation

Maximum leakage of input device: 0.5ma

Response time: all are factory set at 10ms, the user may change

any input to between 0 to 255ms using the Setup Menu

Physical

Size 2.9" (75mm) x 2.2" (55mm) x 4.3" (110 mm)

Mounting DIN rail or panel (with two #6 screws)

Weight 10 oz. (284 grams)

Temp 0 - 140° F, 90% r. humidity (no condensation)

Origin Designed and assembled in the USA.


Part No.     MCU-02-1224 & MCU-04-1224

Power Requirements

12 to 24 VDC @ .3A (30 volts absolute maximum)

Outputs

4 normally open relay contacts unprotected, no leakage current

5Amps @ 230VAC (resistive load), 250 VA (inductive load)

Response time: 10ms operate / 5ms release

Rated life: 5 million (mech) / 200,000 @ 3A (resistive load)

Inputs

6 self powered, 12 VDC @ 10ma. w/1000v optical isolation

Maximum leakage of input device: 0.5ma

Response time: all are factory set at 10ms, the user may change any input to between 0 to 255ms using the Setup Menu

Physical

Size      2.9" (75mm) x 2.2" (55mm) x 4.3" (110 mm)

Mounting      DIN rail or panel (with two #6 screws)

Weight      8 oz. (227 grams)

Temp      0 to 140° F, 90% r. humidity (no condensation)

Origin      Designed and assembled in the USA.

 

Part No.    MCU-02-230 & MCU-04-230

Power Requirements

230VAC @ .01A, 50/60Hz w/1000v magnetic isolation

Outputs

4 normally open relay contacts unprotected, no leakage current

5Amps @ 230VAC (resistive load), 250 VA (inductive load)

Response time: 10ms operate / 5ms release

Rated life: 5 million (mech) / 200,000 @ 3A (resistive load)

Inputs

6 self powered, 12-14 VDC @ 10ma. w/ 1000v optical isolation

Maximum leakage of input device: 0.5ma

Response time: all are factory set at 10ms, the user may change any input to between 0 to 255ms using Setup Menu

Physical

Size      2.9" (75mm) x 2.2" (55mm) x 4.3" (110 mm)

Mounting      DIN rail or panel (with two #6 screws)

Weight    10 oz. (284 grams)

Temp    0 - 140° F, 90% r. humidity (no condensation)

Origin      Designed and assembled in the USA.

Go to specifications directory.